Samsung MIM-B17 Manual do Utilizador Página 98

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 108
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 97
E-97
LonWorks Gateway Setting (Continued)
Description
Fan Speed and direction
SNVT Type
SNVT_switch: Unsigned/signed Short
Value and operation
Value State
Auto 0.0 -
Low 1.0 -
Mid 2.0 -
High 3.0 -
Eco 4.0 -
Turbo 5.0 -
Auto Any>5.0
Stop - 0
Up-Down - 1
Supporting modes are different according to indoor units.
- Indoor unit: Auto, Low, Mid, High
- ERV : Mid, High, Turbo
- AHU Kit: High
* When an indoor unit operation mode is Auto or Dehumid,
Fan speed is controlled as Auto.
* When an indoor unit operation mode is FAN ONLY, Auto’
cannot be controlled by Fan speed.
nvoFanStatus(15), nviFanStatus(4)
Description
ERV Operation Mode
SNVT Type
SNVT_count: Unsigned Long, 2 bytes
Value and operation
( 0: Auto )
1: H/R
( 2: Air purification )
3: Sleep
4: Normal
( ) : Function that is not supported now.
nvoERVMode(16), nviERVMode(5)
Description
Error Code
SNVT Type
SNVT_count: Unsigned Long, 2 bytes
Value and operation
Valid Range: 0 ~ 999
00 00 No Error
Refer to list of Error code
nvoErrorCode(17)
SOL_DMS2&BAC&LW_IBIM_EN_32138A-10_EN_150617.indd 97 2015-06-18 오후 5:34:30
Vista de página 97
1 2 ... 93 94 95 96 97 98 99 100 101 102 103 ... 107 108

Comentários a estes Manuais

Sem comentários