E-97
LonWorks Gateway Setting (Continued)
Description
Fan Speed and direction
SNVT Type
SNVT_switch: Unsigned/signed Short
Value and operation
Value State
Auto 0.0 -
Low 1.0 -
Mid 2.0 -
High 3.0 -
Eco 4.0 -
Turbo 5.0 -
Auto Any>5.0
Stop - 0
Up-Down - 1
Supporting modes are different according to indoor units.
- Indoor unit: Auto, Low, Mid, High
- ERV : Mid, High, Turbo
- AHU Kit: High
* When an indoor unit operation mode is Auto or Dehumid,
Fan speed is controlled as ‘Auto’.
* When an indoor unit operation mode is FAN ONLY, ‘Auto’
cannot be controlled by Fan speed.
nvoFanStatus(15), nviFanStatus(4)
Description
ERV Operation Mode
SNVT Type
SNVT_count: Unsigned Long, 2 bytes
Value and operation
( 0: Auto )
1: H/R
( 2: Air purification )
3: Sleep
4: Normal
( ) : Function that is not supported now.
nvoERVMode(16), nviERVMode(5)
Description
Error Code
SNVT Type
SNVT_count: Unsigned Long, 2 bytes
Value and operation
Valid Range: 0 ~ 999
00 00 → No Error
Refer to list of Error code
nvoErrorCode(17)