E-101
LonWorks Gateway Setting (Continued)
desription character value
ascii.
[0]
Model information
Alphabet or digit
Alphabet or digit
Alphabet or digit
Alphabet or digit
Alphabet or digit
Alphabet or digit
[1]
[2]
[3]
[4]
[5]
[6] Separator Underbar(_) 095
[7]
Centralized controller
address
Alphabet or digit
Alphabet or digit
[8]
[9] Separator Period(.) 046
[10]
Interface Module address
Alphabet or digit
Alphabet or digit
[11]
[12] Separator Period(.) 046
[13]
Indoor Unit Address
Alphabet or digit
Alphabet or digit
[14]
[15] Separator Underbar(_) 095
[16] Unit type 0: indoor unit, 1: AHU, 2: ERV
[17] Separator Underbar(_) 095
[18] Operation mode
DMS Format
0: Auto, 1: Cool, 2: Dehumid,
3: Fan, 4: Heat
[19] ON/OFF 0, 1
[20] Fan speed 0, 1, 2, 3, 4, 5
[21] Fan Swing 0, 1
[22] Error 0, 1
[23] Separator Underbar(_) 095
[24]
setPoint temperate
Second significant digit
First significant digit
First decimal place
[25]
[26]
[27]
Space temperate(*)
Second significant digit
First significant digit
First decimal place
[28]
[29]
[30] Null padding 0 048
(*) If the value is a negative number, it is displayed as sign, 10-digit, single-digit.
Expansion of nvoDevListDesc