Single EHS Unit has following point list.
Instance
Number
Object
Object
Type
Object Name
Unit Status value
Inactive
Active
Text-1 Text-2 Text-3 Text-4
1 Room temperature AI EHS_RoomTemp_xx_xxxxxx °C
2 Set temperature AV EHS_Temp_Set_xx_xxxxxx °C
Use when displayed temperature type
is set to 'Room'.
3 Set temperature of water out AV
EHS_WaterOutTemp_Set_xx_
xxxxxx
°C
Use when displayed temperature type
is set to 'WaterOut'.
4 Set temperature of hot water AV
EHS_HotWaterTemp_Set_xx_
xxxxxx
°C
5 Setting lower temperature limit AV EHS_Cool_LimitTemp_xx_xxxxxx °C
Use when displayed temperature type
is set to 'Room'.
6 Setting upper temperature limit AV EHS_Heat_LimitTemp_xx_xxxxxx °C
Use when displayed temperature type
is set to 'Room'.
7
Lower temperature limit for wa-
ter out
AV
EHS_WOCoolLimitTemp_xx_
xxxxxx
°C
8
Upper temperature limit for wa-
ter out
AV
EHS_WOHeatLimitTemp_xx_
xxxxxx
°C
9
Upper temperature limit for hot
water
AV
EHS_WTHeatlLimitTemp_xx_
xxxxxx
°C
10
The power value after the basic
date
AI EHS_Baseline_kWh_xx_xxxxxx kWh
11
The number of hours usage of an
indoor unit after the basic date
AI EHS_Baseline_Minute_xx_xxxxxx Minute
12 Power value within period AI EHS_Period_kWh_xx_xxxxxx kWh
13
The number of hours usage of an
indoor unit within period
AI EHS_Period_Minute_xx_xxxxxx Minute
14 Current temperature of water out AI EHS_WOCurrentTemp_xx_xxxxxx °C
15 Current temperature of hot water AI EHS_HotWaterTemp_xx_xxxxxx °C
16 Displayed temperature type BI EHS_ControlTempType_xx_xxxxxx Room
WaterOut
17 Thermostat usage BI EHS_Thermostat_xx_xxxxxx False True
18 Outing BI EHS_GoOut_xx_xxxxxx Off On
19 Power On/Off BV EHS_Power_xx_xxxxxx Off On
20 Setting lower temperature limit BV
EHS_Cool_LimitTemp_Set_xx_
xxxxxx
False True
Use when displayed
temperature type is set to
'Room'.
21 Setting upper temperature limit BV
EHS_Heat_LimitTemp_Set_xx_
xxxxxx
False True
Use when displayed
temperature type is set to
'Room'.
22
Apply lower temperature limit for
water out
BV EHS_WOCoolLimitFlag_xx_xxxxxx False True
Use when displayed
temperature type is set to
'WaterOut'.
23
Apply upper temperature limit for
water out
BV EHS_WOHeatLimitFlag_xx_xxxxxx False True
Use when displayed
temperature type is set to
'WaterOut'.
24
Apply upper temperature limit for hot
water
BV EHS_WTHeatLimitFlag_xx_xxxxxx False True
EHS
BACnet Gateway setting (Continued)
SOL_DMS2&BAC&LW_IBIM_EN_32138A-10_EN_150617.indd 70 2015-06-18 오후 5:34:19