E-99
LonWorks Gateway Setting (Continued)
Description
Setting/monitoring upper limit temperature
and function toggle
SNVT Type
SNVT_switch: Unsigned/signed Short
Value and operation
Operation Value State
Unlock 16.0 ~ 30.0 0
Lock 16.0 ~ 30.0 1
Heat: 16.0°C ~ 30.0°C
nvoHeatTempLock(21), nviHeatTempLock(10)
Description
Electric consumption value within the period
SNVT Type
SNVT_elec_kwh_I: Signed Quad, 4bytes
Value and operation
Raw range: 0 ~ 999999
Resolution: 0.1
nvoEnergyConp(23)
Description
Electric consumption value after baselin
SNVT Type
SNVT_elec_kwh_I: Signed Quad, 4bytes
Value and operation
Raw range: 0 ~ 999999
Resolution: 0.1
nvoEnergyCon(24)
Description
Indoor unit usage within the period
SNVT Type
SNVT_time_hour: Signed Long, 2bytes
Value and operation
Raw range: 0 ~ 65535
nvoRunTimep(25)
Description
Indoor unit usage after baseline
SNVT Type
SNVT_time_hour: Signed Long, 2bytes
Value and operation
Raw range: 0 ~ 65535
Energy consumption and Runtime are the accumulated value
during the user setting period.
The data above is for reference so you can not use them for
official billing.
nvoRunTime(26)