E-18
You can set the system settings through contact control
pattern.
Setting the External Contact Control Pattern
Using the DI External Contact Control (Optional)
1
Select [System Settings] menu and click [System
environment setting].
2 Click [Edit] from ‘Select the contact control pattern’.
3
Select the pattern you want to check.
Pattern 1[No external input]: No operation will be made
when inputting contact point control signal.
Pattern 2[Level(Emergency stop)]: Commands that stop
all indoor unit operation and disable remote control
when inputting contact point control signal. In level
emergency stop status, it will not be controlled even if
the command is set from upper controller.
Pattern 3[Level(Operation/Stop)]: Level signal input
timing.
It changes operation/stop status of all indoor units.
Pattern 4[pulse (Operation/Stop,Disable/Enable)]:
Pulse signal. It changes operation/stop status of all
indoor units.
4
Click [Save] after setting is completed.
5
Click [OK] when “This information will be modified. Do
you want to proceed?” message window appears.
6
“Reading data from DMS2. Please wait.” message appears
and saving is completed. Then, system environment
setting screen appears again with all items are disabled.
Note
Pattern 1 is set as factory setting.
DMS2 has total 10 DI ports. However, actually used DI ports
are Ch1 and Ch2, and the rest of the ports (Ch3~Ch10) are
for additional functions. Therefore, make sure to connect
Ch1 or Ch2 when using it.
For DO, Ch1 and Ch2 are currently used inside of DMS2.
Ch9 and Ch10 are reserved in case of need. Therefore you
can only use Ch3~Ch8.
Installing the DMS2 (Continued)
SOL_DMS2&BAC&LW_IBIM_EN_32138A-10_EN_150617.indd 18 2015-06-18 오후 5:34:01