Samsung MIM-B17 Manual do Utilizador Página 97

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 108
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 96
E-96
Message Definition
Description
Indoor temperature
SNVT Type
SNVT_temp_p: Signed Long, 2 bytes
Value and operation
Range: -10.00°C ~ 50.00°C
nvoSpaceTemp(11)
Data for Indoor Device
Description
Operation Mode status
SNVT Type
SNVT_hvac_mode: Enumeration(hvac_t)
Value and operation
0: HVAC_AUTO
1: HVAC_HEAT
3: HVAC_COOL
6: HVAC_OFF
9: HVAC_FAN_ONLY
14: HVAC_DEHUMID
Invalid Value:
Automatically set as HVAC_AUTO
nvoSpaceTemp(11)
Description
Set Temperature
SNVT Type
SNVT_temp_p: Signed Long, 2 bytes
Value and operation
Cool: 18.0°C ~ 30.0°C, Heat: 16.0°C ~ 30.0°C
Invalid Value: Automatically set up as minimum or
maximum value.
When setting temperature, only an integer value is
applied. A decimal point is ignored.
nvoSpaceTemp(11)
Description
Power ON/OFF status
SNVT Type
SNVT_switch: Unsigned/signed Short
Value and operation
Value State
OFF 0.0 0
ON 100.0 1
nvoSpaceTemp(11)
LonWorks Gateway Setting (Continued)
SOL_DMS2&BAC&LW_IBIM_EN_32138A-10_EN_150617.indd 96 2015-06-18 오후 5:34:30
Vista de página 96
1 2 ... 92 93 94 95 96 97 98 99 100 101 102 ... 107 108

Comentários a estes Manuais