E-54
Reading EHP Watt-hour Meter
1
Click [System and Checking Watt-hour meter].
You can change settings on watt-hour meter only when
SIM/PIM interface module is connected.
2
Click [Edit] from the 'Setting and checking Watt-hour
meter' screen.
CT proportion is set to ‘1’ as factory default value.
3
Set the [Name] and [CT proportion] for the watt-hour
meter.
You can use maximum 16 letters for name and only
available special characters are “.”, ”,”, ”_”, ”-“, and
“space”.
Value for CT proportion should be integer between
range of 1 ~ 5000.
4
Click [Save].
CT proportion value will be saved to the BACnet
Gateway.
If you do not click [Save] changed setting will not be
saved.
5
Watt-hour meter value will display the actual value of
electricity on the corresponding watt-hour meter. Value
will be updated automatically.
When using CT watt-hour meter, be careful that there can
be dierence with actual power consumption as much as
CT ratio error.
Setting and checking watt-hour meter
BACnet Gateway setting (Continued)