Single indoor unit has following point list.
Instance
Number
Object
Object
Type
Object Name
Unit Status value
Inactive Active
Text-1 Text-2 Text-3 Text-4 Text-5
1
Indoor temperature AI AC_RoomTemp_xx_xxxxxx
2
Set temperature AV AC_Temp_Set_xx_xxxxxx
3
Setting lower temperature limit AV AC_Cool_LimitTemp_xx_xxxxxx
4
Setting upper temperature limit AV AC_Heat_LimitTemp_xx_xxxxxx
5
The power value of an indoor
unit after the basic date
AI AC_Baseline_kWh_xx_xxxxxx
kWh
6
The number of hours usage of an
indoor unit after the basic date
AI AC_Baseline_Minute_xx_xxxxxx
Minute
7
Power value within period AI AC_Period_kWh_xx_xxxxxx kWh
8
The number of hours usage of
an indoor unit within period
AI AC_Period_Minute_xx_xxxxxx Minute
9
Power On/Off BV AC_Power_xx_xxxxxx Off On
10
Applying lower temperature
limit setting
BV AC_Cool_Limit_set_xx_xxxxxx False True
11
Applying upper temperature
limit setting
BV AC_Heat_Limit_set_xx_xxxxxx False True
12
Filter sign status BI AC_FilterSign_xx_xxxxxx False True
13
Filter sign reset BO AC_FilterSign_Reset_xx_xxxxxx False True
14
Operation mode status MV AC_Operation_Mode_xx_xxxxxx Auto Cool Heat Fan Dry
15
Fan speed status MV AC_FanSpeed_xx_xxxxxx Auto Low Mid High
16
Air flow direction status MV AC_FanFlow_xx_xxxxxx
None Vertical
Horizon
All
17
Operation mode limit status MV AC_Mode_Limit_xx_xxxxxx
No
Limit
Cool
Only
Heat
Only
18
Remote controller limit status MV AC_Remocon_Limit_xx_xxxxxx
Enable
RC
Disable
RC
Conditional
RC
19
Integrated error code of both
indoor unit and outdoor unit
AI AC_Error_Code_xx_xxxxxx Refer to Samsung integrated error code list
20
(7)
SPI setting BV AC_SPI_xx_xxxxxx False True
21
(7)
HumanSensor setting BV AC_MDS_xx_xxxxxx False True
22
(7)
AC Indoor Notify NC AC_Notify_xx_xxxxxx
When the error occurred, send event to list of
destination in the recipient_list. (Max : 8)
Ú Temperature setting range can be different depending on the model and the common range is as follows :
Auto : 18˚C~30˚C
Cool : 18˚C~30˚C
Heat : 16˚C~30˚C
Fan : Temperature cannot be adjusted
Dry : 18˚C~30˚C
(7)
Mark is optionally supported.
7) Object list
(1) Indoor unit
Vista de página 8
1 2 3 4 5 6 7 8 9 10 11 12 13 14 ... 22 23

Comentários a estes Manuais

Sem comentários