Samsung MIM-B17 Manual do Utilizador Página 11

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 23
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 10
131
B
UILDING
M
ANAGEMENT
S
YSTEM
(3) ERV
(4) SIM
(5) On/Off Controller
(6) Interface module (Outdoor unit)
Instance
Number
Object
Object
Type
Object Name
Unit Status value
Inactive Active
Text-1 Text-2 Text-3 Text-4 Text-5
1
Power On/Off operation BV ERV_Power_xx_xxxxxx
Off
On
2
Filter sign status BI ERV_FilterSign_xx_xxxxxx False True
3
Filter sign reset BO ERV_FilterSign_Reset_xx_xxxxxx False True
4
Operation mode status MV ERV_Operation_Mode_xx_xxxxxx Auto
HeatEx Bypass Sleep
5
Fan speed status MV ERV_FanSpeed_xx_xxxxxx
Low High Turbo
6
Remote controller limit status
MV ERV_Remocon_Limit_xx_xxxxxx
Enable
RC
Disable
RC
Conditional
RC
7
Integrated error code of ERV
unit
AI ERV_Error_Code_xx_xxxxxx Refer to list of error code
8
ERV Notify NC ERV_Notify_xx_xxxxxx
When the error occurred, send event to list
of destination in the recipient_list. (Max : 8)
Instance
Number
Object
Object
Type
Object Name
Unit Status value
Inactive Active
Text-1 Text-2 Text-3 Text-4 Text-5
1
Outside temperature AI ODU_Outside_Temp_xx_xxxx
°C
2
(7)
Cool capacity compensation AV
ODU_Cool_Compensation_xx_
xxxx
0 : 5~7°C / 1 : 7~9°C / 2 : 9~11°C /
3 : 10~12°C / 4 : 11~13°C / 5 : 12~14°C /
6 : 13~15°C / 14 : Auto control (from ODU)
3
(7)
Heat capacity compensation AV
ODU_Heat_Compensation_xx_
xxxx
0 : 25kg/cm² / 1 : 26kg/cm² /
2 : 27kg/cm² / 3 : 28kg/cm² /
4 : 29kg/cm² / 5 : 30kg/cm² /
6 : 31kg/cm² / 7 : 32kg/cm² /
8 : 33kg/cm² / 14 : Auto control (from ODU)
4
Compressor status BI ODU_Comp_Status_xx_xxxx False
True uu
5
Interface module error code AI Repeater_Error_Code_xx_xxxx
Refer to the list of the integrated error code
6
Interface module notify
NC IM_Notify_xx_xxxx
When the error occurred, send event to list
of destination in the recipient_list. (Max : 8)
Instance
Number
Object
Object
Type
Object Name Status value
1
SIM error code AI SIM_Error_Code_xx_xx Refer to list of error code
2
SIM Notify NC SIM_Notify_xx_xx
When the error occurred, send event
to list of destination in the recipient_list. (Max : 8)
Instance
Number
Object
Object
Type
Object Name Status value
1
On/Off Controller
error code
AI Central_Error_Code_xx_xx
Refer to the list of the integrated
error code
2
On/Off Controller
notify
NC Central_Notify_xx_xx
When the error occurred, send
event to list of destination in the
recipient_list. (Max : 8)
(7)
Mark is optionally supported.
Single ERV unit has following point list.
Single SIM has following point list.
Single On/Off Controller has following point list.
Single Interface(Outdoor unit) module has following point list.
Vista de página 10