Samsung MIM-B17 Manual do Utilizador Página 7

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 23
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 6
127
B
UILDING
M
ANAGEMENT
S
YSTEM
Connecting with outdoor unit and on/off controller
Wiring distance
Maximum 16
outdoor units
1
2
3
f Distance between BACnet Gateway and On/Off controller/outdoor unit
Distance from the BACnet Gateway to the furthest device cannot exceed 1000m.
+
+
d 1000m
f Distance between BACnet Gateway and upper level controller
Since BACnet Gateway supports 100 Base-T Ethernet, first repeater or upper level controller from the BACnet Gateway
cannot be further than 100m (IEEE 802.3). Therefore, maximum network radius is restricted to 500m.
DMS-Bnet
Network radius
Maximum 15 On/Off controllers or
16 outdoor units can be connected
to 1 channel of the BACnet Gateway
DMS-Bnet
HUB
Repeater
Maximum number of repeaters = 4
500m
,
,
,
,
= 100m
Outdoor unit
Outdoor unit
Outdoor unit
R1R2 R1R2R1R2
BACnet Gateway
Vista de página 6
1 2 3 4 5 6 7 8 9 10 11 12 ... 22 23

Comentários a estes Manuais

Sem comentários