Vista de página 11
Control Systems
132
9,9,
Building management system
(7) BACnet Gateway
(8) Digital input / output
2. BACnet Gateway
7) Object list
󰞃 MIM-B17N
BACnet Gateway has following point list.
Digital input / output Gateway has following point list.
Instance
Number
Control and
Monitoring
Object
Type
Object Name Status value
1
All device OFF BO ALL_OFF_xx Inactive : All devices Off
1
DMS2 Status AI DMS2_Status_xx
0: Normal, 8: Emergency stop,
105 : Tracking in progress,
108 : Tracking failed
109 : DMS2 ¥ BACnet
Communication failed
1
BACnet error code AI
BACnetApp_Error_
Code_xx
BACnet error code
2
Gateway Notify NC GW_Notify_xx
When the error occurred, send event to list
of destination in the recipient_list. (Max : 8)
Instance
Number
Object
Object
Type
Object Name
Unit Status value
Inactive Active
Text-1 Text-2 Text-3 Text-4 Text-5
1
Digital Input 1 BI DI_01_xx_xx (BACnet Gateway Reserved)
Off
On
2
Digital Input 2 BI DI_02_xx_xx (BACnet Gateway Reserved)
Off
On
3
Digital Input 3 BI DI_03_xx_xx
Off
On
4
Digital Input 4 BI DI_04_xx_xx
Off
On
5
Digital Input 5 BI DI_05_xx_xx
Off
On
6
Digital Input 6 BI DI_06_xx_xx
Off
On
7
Digital Input 7 BI DI_07_xx_xx
Off
On
8
Digital Input 8 BI DI_08_xx_xx
Off
On
9
Digital Input 9 BI DI_09_xx_xx
Off
On
10
Digital Input 10 BI DI_10_xx_xx
Off
On
11
Digital Output 1 BO
DO_01_xx_xx (BACnet Gateway Reserved)
Off
On
12
Digital Output 2 BO
DO_02_xx_xx (BACnet Gateway Reserved)
Off
On
13
Digital Output 3 BO
DO_03_xx_xx
Off
On
14
Digital Output 4 BO
DO_04_xx_xx
Off
On
15
Digital Output 5 BO
DO_05_xx_xx
Off
On
16
Digital Output 6 BO
DO_06_xx_xx
Off
On
17
Digital Output 7 BO
DO_07_xx_xx
Off
On
18
Digital Output 8 BO
DO_08_xx_xx
Off
On
f Caution
You may use ALL_OFF command to turn on all the indoor units but it is not recommended.
If communication error occurs on devices such as SIM/On/Off Controller/Interface Module etc, other functions such as
power distribution may also create a problem. You must have BMS system to check the errors and you must take action
immediately.