
141
B
UILDING
M
ANAGEMENT
S
YSTEM
(5) Binary output property
Property identifier Property data
Check
code
Support
DMS2
1 Object identifier BACnetObjectIdentifier R V
2 Object name CharaterString R V
3 Object type BACnetObjectType R V
4 Present value BACnetBinaryPV W V
5 Description CharacterString O V
AI_Instance_device
address
6 Device type CharacterString O
7 Status Flags BACnetStatusFlags R V
Communication
Status_Flags FAULT flag
True OUT_OF_SERVICE
TRUE
8 Event state BACnetEventState R V
General Error
Status_Flags FAULT flag
TRUE
FAULT if Reliability is not
NO_FALUT_DETECTED
Communication error
COMMUNICATION_
FAILURE
General error
Unreliable_other
9 Reliability BACnetReliability O V
10 Out of service BOOLEAN R V
Communication error
TRUE
11 Polarity BACnetPolarity R V
12 Inactive text CharacterString
O
(1)
V
13 Active text CharacterString
O
(1)
V
14 Change of state time BACnetDateTime
O
(2)
15 Change of state count Unsigned
O
(2)
V
16 Time of State count reset BACnetDateTime
O
(2)
O
(3)
V
17 Elapsed active time Unsigned32
O
(3)
18 Time of active time reset BACnetDate Time
O
19 Minimum off time Unsigned32
O
20 Minimum on time Unsigned32
O
21 Priority array BACnetPriorityArray
R
22 Relinquish default BACnetBinaryPV
R
23 Time delay Unsigned
O
(4)
24 Notification class Unsigned
O
(4)
25 Alarm value BACnetBinaryPV
O
(4)
26 Event enable BACnetEventTransitionBits
O
(4)
27 Acked transition BACnetEventTransitionBits
O
(4)
28 Notify type BACnetNotifyType
O
(4)
Comentários a estes Manuais