Control Systems
142
9,9,
Building management system
2. BACnet Gateway
10) Property support specification
(6) Multi-state input property
MIM-B17N
Property identifier Property data
Check
code
Support
DMS2
1 Object identifier BACnetObjectIdentifier R V
2 Object name CharaterString R V
3 Object type BACnetObjectType R V
4 Present value Unsigned R(1) V
5 Description CharacterString O V
M_Instance_device
address
6 Device type CharacterString O
7 Status Flags BACnetStatusFlags R V
Communication
Status_Flags FAULT flag
True OUT_OF_SERVICE
TRUE
8 Event state BACnetEventState R V
General Error
Status_Flags FAULT flag
TRUE
FAULT if Reliability is not
NO_FALUT_DETECTED
Communication error
COMMUNICATION_
FAILURE
General error
Unreliable_other
9 Reliability BACnetReliability O V
10 Out of service BOOLEAN R V
Communication error
TRUE
11 Number of states Unsigned R V
12 State text
BACnet sequence of
characterString
O
V
13 Time delay Unsigned
O
(2)
14 Notification class Unsigned
O
(2)
15 Alarm values Unsigned list
O
(2)
16 Fault values Unsigned list
O
(2)
17 Event enable BACnetEventTransitionBits
O
(2)
18 Acked transition BACnetEventTransitionBits
O
(2)
19 Notify type BACnetNotifyType
O
(2)