Control Systems
130
9,9,
Building management system
(2) AHU kit
2. BACnet Gateway
7) Object list
󰞃 MIM-B17N
Instance
Number
Object
Object
Type
Object Name
Unit Status value
Inactive Active
Text-1 Text-2 Text-3 Text-4 Text-5
1
Indoor Temperature AI AHU_RoomTemp_xx_xxxxxx
2
Set temperature AV AHU_Temp_Set_xx_xxxxxx
3
Setting lower temperature limit AV AHU_Cool_LimitTemp_xx_xxxxxx
4
Setting upper temperature limit AV AHU_Heat_LimitTemp_xx_xxxxxx
5
The power value of an indoor
unit after the basic date
AI AHU_Baseline_kWh_xx_xxxxxx
kWh
6
The number of hours usage of an
indoor unit after the basic date
AI AHU_Baseline_Minute_xx_xxxxxx
Minute
7
Power value within period AI AHU_Period_kWh_xx_xxxxxx kWh
8
The number of hours usage of
an indoor unit within period
AI AHU_Period_Minute_xx_xxxxxx Minute
9
Power On/Off BV AHU_Power_xx_xxxxxx Off On
10
Applying lower temperature
limit setting
BV AHU_Cool_Limit_set_xx_xxxxxx False True
11
Applying upper temperature
limit setting
BV AHU_Heat_Limit_set_xx_xxxxxx False True
12
Filter sign status BI AHU_FilterSign_xx_xxxxxx False True
13
Filter sign reset BO AHU_FilterSign_Reset_xx_xxxxxx False True
14
Operation mode status MV AHU_Operation_Mode_xx_xxxxxx Auto Cool Heat Fan Dry
15
Operation mode limit status MV AHU_Mode_Limit_xx_xxxxxx
No
Limit
Cool
Only
Heat
Only
16
Remote controller limit status MV AHU_Remocon_Limit_xx_xxxxxx
Enable
RC
Disable
RC
Conditional
RC
17
Integrated error code of both
indoor unit and outdoor unit
AI AHU_Error_Code_xx_xxxxxx Refer to Samsung integrated error code list
18
(7)
Discharge cooling set
temperature
AV AHU_DisCoolSetTemp_xx_xxxxxx °C
19
(7)
Discharge heating set
temperature
AV AHU_DisHeatSetTemp_xx_xxxxxx °C
20
(7)
Discharge current
temperature
AI AHU_Dis_CurrentTemp_xx_xxxxxx °C
21
(7)
Humidification setting BV AHU_Humidification_xx_xxxxxx Off On
22
(7)
Outdoor air intake setting BV AHU_OAIntake_xx_xxxxxx Off On
23
(7)
Outdoor cooling setting BV AHU_OutdoorCool_xx_xxxxxx Off On
24
(7)
Fan speed status MV AHU_FanSpeed_xx_xxxxxx Low Mid High
25
(7)
Set humidity status MV AHU_SetHumidity_xx_xxxxxx Low Mid High
26
(7)
Current humidity status MI AHU_CurrentHumidity_xx_xxxxxx Low Mid High
27
AHU Notify NC AHU_Notify_xx_xxxxxx
When the error occurred, send event to list
of destination in the recipient_list. (Max : 8)
(7)
Mark is optionally supported.
Single AHU unit has following point list.