4. Indoor Units installation
94
① Install main air vent at the front of the farthest indoor unit from the main drain when installed
indoor units are more than 3.
② You may need to install individual air vent to prevent water flow back at the top of each
indoor unit drainpipe.
AIR-VENT interval of 10m~15m. Drainpipe hanger fixed within 1~1.5m.
If the interval is more than 1~1.5m, bending of the PVC pipe can cause poor water drainage.