(7) Decoration panel installation
(8) Drain installation
The drainpipe should be installed within 100mm from the flexible hose, lift up from 100mm to
550mm and lift down 20mm or more.
Install horizontal drainpipe with a slope of 1/100 or more and fix it by hanger space of
1~1.5m.
Install the air vent in the horizontal drainpipe to prevent water flow back to the indoor unit.
- You may not need to install it if there were proper slope in the horizontal drainpipe.
The flexible hose should not be installed upward position, it may cause water flow back to
the indoor unit.
Install U-trap at the end of the drainpipe to prevent a nasty smell to reach the indoor unit.