Page 4 of 97 Report No. 236145
TRF No. IEC60335_2_40F
Summary of testing:
Tests performed (name of test and test clause):
- Clause 7: Marking and instructions
- Clause 8: Protection against access to live parts
- Clause10: Power input and current
- Clause 11: Heating
- Clause 13: Leakage current and electric strength at
operating temperature
- Clause 15: Moisture resistance
- Clause 16: Leakage current and electric strength
- Clause 19: Abnormal operation
- Clause 20: Stability and mechanical hazards
- Clause 21: Mechanical strength
- Clause 22: Construction
- Clause 23: Internal wiring
- Clause 24: Components
- Clause 25: Supply connection and external flexible
cord
- Clause 26: Terminals for external conductors
- Clause 27: Provision for earthing
- Clause 28: Screws and connections
- Clause 29: Clearances, creepage distances and
solid insulation
- Clause 30: Resistance to heat and fire
- Annex E: Needle flame test
- Annex N: Proof tracking test
- Annex EE: Pressure test
Testing location:
Samsung Electronics Co., Ltd.
Digital Air-solutions Business Team,
129, Samsung-ro, Yeongtong-gu, Suwon-si,
Gyeonggi-do, 443-742 Korea, Republic of
1. Safety test conditions;
Normal temperature condition was considered as following based on ISO 13253 and ISO 15042;
- For climatic class T1, an appliance was installed with the indoor side subjected to 27C and the outdoor
side subjected to 35C for cooling function.
- For climatic class T3, an appliance was installed with the indoor side subjected to 29C and the outdoor
side subjected to 46C for cooling function.
- An appliance was installed with the indoor side subjected to 20C and the outdoor side subjected to 7C for
heating function.
2. EMF test conditions;
1) Measuring distance (r1): 30 cm
2) Sensor locations: Around
3) Operating conditions: Continuously.
Cooling mode: Lowest cooling, Heating mode: Highest heating
3. In this test report, the model AM140FNHDEH (indoor unit, built-in duct type) was mainly tested and
evaluated as a representative by connecting it with the model AM100FXVAGH (outdoor unit).
4. Heat exchanger of this appliance was tested and evaluated with the refrigerant R410A only in this test
report.
5. The appliance shall be provided with a certified supply cord and interconnection cords complying with the
national regulations of the countries in which the appliance is to be sold. The supply cord and
interconnection cords were evaluated just for the reference in this test report.