installation part _43
AIR PURGE
Be sure that all valve cocks are closed.
The air in the indoor unit and in the pipe must be purged. If air remains in the refrigeration pipes, it will
affect the compressor, reduce to cooling capacity and could lead to a malfunction.
Use Vacuum Pump as shown at the figure.
1. Connect each assembly pipe to the appropriate valve on the outdoor unit and tighten the flare nut.
2. Connect the charging hose of low pressure side of manifold gauge to the packed valve having a service
port as shown at the figure.
3. Open the valve of the low pressure side of manifold gauge counter-clockwise.
4. Purge the air from the system using vacuum pump for about 10 minutes.
- Close the valve of the low pressure side of manifold gauge clockwise.
- Turn off the vacuum pump.
- Make sure that pressure gauge show -0.1MPa(-76cmHg) after about 10 minutes.
- This procedure is very important in order to avoid gas leak.
- Remove the hose of the low pressure side of manifold gauge.
5. Set valve cork of both liquid side and gas side of packed valve to the open position.
6. Mount the cap and the needle valve cap to the valve (see the below illustration), and tighten them at
the torque of 183kgf•cm with a torque wrench.
7. Check for gas leakage.
- At this time, especially check for gas leakage from the 3-way valves stem nuts, and from the service
port cap.
A
B
OUTDOOR UNIT
Gas pipe
side
Vacuum
Pump
Liquid
pipe side
Needle valve
cap
Flare nut
Valve cock
Cap
Indoor unit
3-way valve
Outdoor unit
3-way valve
Gas pipe sideLiquid pipe side
AP36M0A_IBIM_E_DB98-33839A-1.indd 43 2011-06-10 오후 1:38:09