E-58
BACnet Point List (Continued)
Single AHU unit has following point list.
Instance
Number
Object
Object
Type
Object Name
Unit Status value
Inactive
Active
Text-1 Text-2 Text-3 Text-4 Text-5
1 Indoor Temperature AI
AHU_RoomTemp_xx_
xxxxxx
°C
2 Set temperature AV
AHU_Temp_Set_xx_
xxxxxx
°C
3
Setting lower
temperature limit
AV
AHU_Cool_
LimitTemp_xx_xxxxxx
°C
4
Setting upper
temperature limit
AV
AHU_Heat_
LimitTemp_xx_xxxxxx
°C
5
The power value of an
indoor unit after the
basic date
AI
AHU_Baseline_kWh_
xx_xxxxxx
kWh
6
The number of hours
usage of an indoor unit
after the basic date
AI
AHU_Baseline_
Minute_xx_xxxxxx
Minute
7
Power value within
period
AI
AHU_Period_kWh_xx_
xxxxxx
kWh
8
The number of hours
usage of an indoor unit
within period
AI
AHU_Period_Minute_
xx_xxxxxx
Minute
9 Power On/O BV
AHU_Power_xx_
xxxxxx
O On
10
Applying lower
temperature limit setting
BV
AHU_Cool_Limit_set_
xx_xxxxxx
O On
11
Applying upper
temperature limit setting
BV
AHU_Heat_Limit_set_
xx_xxxxxx
O On
12 Filter sign status BI
AHU_FilterSign_xx_
xxxxxx
O On
13 Filter sign reset BO
AHU_FilterSign_
Reset_xx_xxxxxx
O On
14 Operation mode status MV
AHU_Operation_
Mode_xx_xxxxxx
Auto Cool Heat Fan Dry
15
Operation mode limit
status
MV
AHU_Mode_Limit_xx_
xxxxxx
No
Limt
Cool
Only
Heat
Only
16
Remote controller limit
status
MV
AHU_Remocon_Limit_
xx_xxxxxx
Work
Fully
Limited
Power
On
Limited
17
Integrated error code
of both indoor unit and
outdoor unit
AI
AHU_Error_Code_xx_
xxxxxx
Refer to list of error code