Samsung MIM-B17 Manual de Instalação Página 29

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 64
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 28
E-29
System Settings
5
When the pop-up window appears, click [OK].
6
If you click [OK], current internet explorer will be closed. Then you may run the
web browser again and access to BACnet Gateway by entering the IP set and
saved manually.
Note Factory setting is as follows.
1. IP address: 192.168.0.100
2. Subnet mask: 255.255.255.0
3. Default gateway: 192.168.0.1
4. DNS server: 0.0.0.0
Since BACnet Gateway sets 192.168.0.254 as engineering IP internally, it should
be always available regardless of current IP.
If several BACnet Gateways are connected to single website, there can be IP crash
because same service engineer IP(192.168.0.254)is applied to each BACnet.
In this case, edit the service engineer IP by following below instructions and then
use the IP.
1. Run DOS command window by enteringcmd” from Windows “Start Run.
2. Access to BACnet Gateway by running “telnet 192.168.0.254”from DOS
command window.
3. Enter ID/PASSWORD.
4. Edit sysenv” file (IP setting related file) as below.
- Run sudo vi /mnt/nand0/config/sysenvfrom telnet connection screen.
- Find“IP2=192.168.0.254and edit the IP as you want.
Basic commands
‘i’- Modification is possible after entering
‘x’- Delete
Esc +:wqEnd after saving.
- Restart
5. After editing you may access BACnet Gateway with changed IP.
There can be IP (192.168.0.254) crash if you execute above procedure when
several DMS units are connected. To check accurate operation, change the
service IP after installing each BACnet Gateway.
5
MIM-B17_BACnet Gateway_IM_E 32390-3.indd 29 2011-04-04 오후 3:44:28
Vista de página 28
1 2 ... 24 25 26 27 28 29 30 31 32 33 34 ... 63 64

Comentários a estes Manuais

Sem comentários