Troubleshooting (Continued)
Problem Check Explanation/Solution
Indoor units are
turned on/off by
themselves
Isn’t a schedule or peak control
executing?
Indoor units can be turned on/
off by schedules or peak control.
Are indoor units controlled
individually by wired/wireless
remote controllers?
Set the use of wired/ wireless
remote controllers prohibited.
Peak power control is
out of order
Does the DMS communication
have any problem?
Check the DMS communicates
with the interface module.
It is impossible to control peak
power if the DMS does not
function properly.
Are the indoor units set as
either [Priority Control Mode]
or [Rotation Control Mode]?
Set the indoor units as either
[Priority Control Mode] or
[Rotation Control Mode] using
[Peak Demand]
[Peak power control mode].
Indoor units are not
controlled by
schedule
Isn’t the schedule set as [STOP]?
Start the schedule using
[Schedule] 
[View Daily Schedule].
Is the DMS time set to the
current local time?
Set the DMS time identical to
the current local time.
Schedules are not
displayed
Isn’t the schedule set as [STOP]?
[View Daily Schedule] only
displays currently active
schedules.