When using ELB for 1 phase
Power Supply
Electrical component box
Indoor Unit
Main power cable
Communication
cable&Connection cord
Cable
clamp
Outdoor unit
You should connect the power cable into the power cable terminal and fasten it with a clamp.
The unbalanced power must be maintained within 2% of supply rating.
- If the power is unbalanced greatly, it may shorten the life of the condenser.
If the unbalanced power is exceeded over 4% of supply rating,
the indoor unit is protected, stopped and the error mode indicates.
To protect the product from water and possible shock, you should keep the power cable and the connection cord of the
indoor and outdoor units in the iron pipe.
Ensure that main supply connection is made through a switch that disconnects all poles, with contact gap of a least 3 mm.
Must keep the cable in a protection tube.
Keep distances of 50mm or more between power cable and communication cable.
CAUTION