Vista de página 21
E-22
Appendix
DI-2 DI-1 DO-2 DO-1
2 341
5
DI-1
(Digital Input)
External contact signal control
(ON/OFF control of all the indoor units)
DI-2
(Digital Input)
External contact signal control
(ON/OFF control of all the indoor units)
DO-1
(Digital Output)
Outputs 12V if at least one indoor unit is running.
( External circuit may be built for display using the 12V
output)
Equivalent to the A/C Running’ LED on the DMS external
display.
Outputs as the settings on the Operation mode of A/C
Running LED.
- DMS status: Green light will flicker every 5 seconds
when DMS operates normally.
- Running status of indoor unit: Solid green light will
turn on when the indoor units operate
normally. (at least 1 indoor unit)
DO-2
(Digital Output)
Outputs 12V if there is an error on the indoor or outdoor
unit or if communication error occurs.
( External circuit may be built for display using the 12V
output)
Equivalent to the ‘Error’ LED on the DMS external display.
Serial communication
port
for environment setup purpose.
Note Consult Samsung Electronics when building an
external circuit for display.
DI/DO circuit (Optional)